Flat cell filters type FyaP
FyaP type filters are designed for rough, preliminary purification of atmospheric air supplied to premises for various purposes by ventilation and air conditioning systems.
How to order
Leave a request and we will contact you to clarify the details of your order and select the necessary equipment.
Technical characteristics of cellular flat filters (FCF)
| Filter class according to GOST R 51251-99, EN 779 (Eurovent 4/9) | Specific air load, m3/h, m2 | Resistance, Pa | Cleaning efficiency, % | |
|---|---|---|---|---|
| initial | recommended final | |||
| G3 (EU3) | 7000-9000 | 43-55 | 130 | 54 |
The filters are operational and retain their technical characteristics at the temperature of the air being purified from –400 C to +700 C
The environment and filtered air must not contain aggressive gases and vapors.
The filter parameters were determined in accordance with GOST R 51251-99 “Guidelines for testing and evaluation of air filters for supply ventilation and air conditioning systems.”
Main sizes
| FiP filter index | Overall dimensions, mm | Filter capacity, m 3 /h | ||
|---|---|---|---|---|
| height A | width B | depth L | ||
| 3050 | 500 | 500 | 48 | 1750-2250 |
| 3052 | 592 | 592 | 48 | 2450-3150 |
| 3051 | 592 | 287 | 48 | 1200-1500 |
| 3054 | 592 | 490 | 48 | 2000-2600 |
| 3053 | 287 | 490 | 48 | 1000-1260 |
| 3056 | 610 | 610 | 48 | 2600-3350 |
| 3055 | 610 | 305 | 48 | 1300-1650 |
| 30501 | 287 | 287 | 48 | 570-750 |
| 30505 | 305 | 305 | 48 | 650-850 |
| 3058 | 287 | 892 | 48 | 1800-2300 |
| 3059 | 892 | 490 | 48 | 3050-3950 |
| 3057 | 892 | 592 | 48 | 3700-4750 |
*Filters of other sizes can be produced upon request.
General design of cellular flat filters (FCF)
FYaP filters consist of a frame made of cardboard or galvanized steel, inside of which a volumetric filter material is placed, supported on the air outlet side by a frame mesh.
Maintenance of cell flat filters (FCF)
During the operation of filters, their aerodynamic resistance should be monitored according to the readings of a pressure gauge connected to fittings located in the walls of the air-cleaning chambers before and after the filters. When the differential pressure recommended for a given filter is reached, or based on the available pressure in the system, the filters must be replaced.