Flat cell filters type FyaP5 and FyaP10 for fan coil units
Panel filters FyaP5 and FyaP10 for fan coils provide rough cleaning of the air supplied to the premises and protect the internal surfaces of fan coils from contamination.
How to order
Leave a request and we will contact you to clarify the details of your order and select the necessary equipment.
Technical requirements and characteristics of cellular flat filters for fan coil units (FyaP5 and FyaP10)
| Filter type | Cleaning class GOST R 51251-99 (EN 779) | Specific air load m 3 / h * m 2 (speed, m/s) | Initial aerodynamic drag | Filter sizes, mm | |
|---|---|---|---|---|---|
| depth | width and height | ||||
| FyaP 5 | G2 | 5400(1.5) | 15 | 5 | made to order |
| FyaP10 | G2 | 5400(1.5) | 20 | 10 | |
General design of cellular flat filters for fan coil units (FyaP5 and FyaP10)
The FyaP5 filter consists of a frame made of a rod covered with filter material. Depending on the manufactured dimensions, the rod frame is equipped with additional jumpers to maintain the filter material in the air flow. The FyaP10 filter consists of a galvanized frame 10 mm thick, inside which the filter material is installed. A supporting mesh is installed on the entrance and
exit sides. Depending on the size, FyaP10 filters can also be equipped with additional jumpers. The filters are operational and retain their technical characteristics at the temperature of the air being purified from –400 C to +700 C.
Maintenance of cell flat filters for fan coil units (FyaP5 and FyaP10)
Filters FyaP5 and FyaP10 are disposable and cannot be regenerated. After complete contamination (reaching the final resistance), the filters must be replaced. The manufacturer reserves the right to make changes to the design without compromising the technical characteristics of the product.